DES

DES

The DES Series Hood Exhaust System Units are ideal solutions for compact kitchen utensils such as hotels, food factories, hospitals, shopping malls, food courts and airports.
While cooking in the kitchen, the steam is collected by the hood, and the steam is exhausted to the outside, and the fresh air (make-up air) is passed through the heat recovery heat exchanger and transferred to the hoo

The DES Series Hood Exhaust System Units are ideal solutions for compact kitchen utensils such as hotels, food factories, hospitals, shopping malls, food courts and airports.
While cooking in the kitchen, the steam is collected by the hood, and the steam is exhausted to the outside, and the fresh air (make-up air) is passed through the heat recovery heat exchanger and transferred to the hoo
Supply Air Louver
Prevents impurities that enters the system.
Supply Air Fan
Backward curved Aluminum centrifugal fans are used in the unit to ensure easy servicing/cleaning.
Heat Recovery Exchanger
The Aluminum plate heat recovery exchanger consists of flat Aluminum plates sewed together on the edge.The sewing progress ensures leakage free design.The exchanger is designed so that it is easy to clean.
Exhaust Air Fan
Discharges the cooking gases delivered by the hood. Backward curved Aluminum centrifugal fans are used in the unit to ensure servicing/cleaning.
Exhaust Discharge
Discharges exhaust air vertically to prevent by-pass to supply air.It protects exhaust fan and motor against external effects.
Pre-filter
To increase indoor air quality and to protect the equipments used in unit, ISO Course % 45 class filters (according to ISO 16890 standard) are used in DES units.
Fine Filter
To remove dust and particles that still exists after pre-filtration, M class bag filters (according to ISO 16890 standard) are used
Metal Filter
Holds lubricants in exhaust air. It is made of corrosion resistant aluminum material and washable.
Device Body
The unit’s casing is made up of double skinned high corrosion resistive galvanize coated steel. 50 mm thickness and 70kg/m³ density of Rockwool insulation between the walls is used for thermal and sound insulation. The case of unit is painted by electrostatic powdered paint.
Weather Proof Plate
Protects the unit from unfavorable weather conditions (rain etc.)
Drain Pan
It is installed to discharge the drainage water which comes from the heat exchanger. It is made of Stainless Steel.
Roof Curb
Located between the unit and the roof construction and is used as a mounting base. Obtains air tightness on the roof for both exhaust and supply air ducts.
Heating Coil
After fresh air leaves from heat exchanger,it is heated up to demanded indoor air temperature by heating coil.Water inlet and outlets can be designed at bottom, inside suspended roof. No additional drilling on the roof is required.
Electrical and Control Equipment
The unit is designed so that it is easy to start up and make electrical operation.